TS-385M60RM/4 Type 1 Surge Suppressor

♦ WARNING:  

1. The device must be installed by electrically skilled person, conforming to national standards and safety regulations.

2. It is recommended that installation should be done under power off condition.

Category:

TS Series Three Phases Type 1 Surge Suppressor is designed according to IEC 61643-11 / GB 18802.11. to protect low voltage devices from surge damages, mainly used in power supply system such as power distribution-room, distribution-cabinet and other important power supply system; widely used to protect mobile communication station, telecommunication center, airport, finance, and so on. For installation at LPZ 0A -1 or higher, applied in Surge Suppressor Type 1 for various power supply system.

Similar & Related Power Supply Surge Protectors

TS-385M60RM 4-Type-1-Surge-Suppressor-Widely-Used

♦ Product Size

TS-385M60RM 4-Type-1-Surge-Suppressor-Professional

♦ Basic Circuit Diagram(4+0)

TS-385M60RM 4-Type-1-Surge-Suppressor-High-Efficiency

♦ Basic Circuit Diagram(3+1)

TS-385M60RM 4-Type-1-Surge-Suppressor-Picture

♦ Technical Data of TS-385M60,50,40,30RM/4

Model Number 

4+0 for TN-S system

 TS-385M60RM/4 

(4P) 

TS-385M50RM/4 

(4P) 

TS-385M40RM/4 

(4P) 

TS-385M30RM/4 

(4P) 

Rated voltage (max. continuous voltage)Uc385V~385V~385V~385V~
Nominal discharge current (8/20)In60 KA50 KA40 KA30 KA
Max. discharge current (8/20)Imax120 KA100KA80 KA60 KA
Voltage protection levelUp≤ 2.5KV≤ 2.2KV≤ 2KV≤ 1.8KV
Response timetA≤ 25ns
Max. back up fuse (L) 200AgL/gG
Max. back up fuse (L-L’) 125AgL/gG
Operating temperature rangeTu-40°C…+80°C
Relative humidity: ≤95% (25°C)
Cross-sectional area 35mm2 solid / 50 mm2 flexible
Mounting on 35mm2 DIN rail
Enclosure material Grey/Red thermoplastic, UL94-V0
Dimension 8 mods
Standards IEC 61643-11; GB 18802.11
Type of remote signalling contact Switching contact
Switching capacityU/IAC:250V/0.5A DC:250V/0.1A,125V/0.2A,75V/0.5A
Cross-sectional area for remote

signalling contact

 Max. 1.5mm2 solid / flexible
Certification CE (LVD, EMC & RoHS)
 
♦ Technical Data of TS-275M60,50,40,30RM/4
Model Number 

4+0 for TN-S system

 TS-275M60RM/4 

(4P) 

TS-275M50RM/4 

(4P) 

TS-275M40RM/4 

(4P) 

TS-275M30RM/4 

(4P) 

Rated voltage (max. continuous voltage)Uc275V~275V~275V~275V~
Nominal discharge current (8/20)In60 KA50 KA40 KA30 KA
Max. discharge current (8/20)Imax120 KA100KA80 KA60 KA
Voltage protection levelUp≤ 2.2KV≤ 2.0KV≤ 1.8KV≤ 1.5KV
Response timetA≤ 25ns
Max. back up fuse (L) 200AgL/gG
Max. back up fuse (L-L’) 125AgL/gG
Operating temperature rangeTu-40°C…+80°C
Relative humidity: ≤95% (25°C)
Cross-sectional area 35mm2 solid / 50 mm2 flexible
Mounting on 35mm2 DIN rail
Enclosure material Grey/Red thermoplastic, UL94-V0
Dimension 8 mods
Standards IEC 61643-11; GB 18802.11
Type of remote signalling contact Switching contact
Switching capacityU/IAC:250V/0.5A DC:250V/0.1A,125V/0.2A,75V/0.5A
Cross-sectional area for remote

signalling contact

 Max. 1.5mm2 solid / flexible
Certification CE (LVD, EMC & RoHS)
 

 MAIN CHARACTER 

1, High discharge capacity, quick response
2, Consist of varistor and thermal disconnection device
3, Double terminals for parallel or series (V-shape) connection
4, Multifunctional connection for conductors and busbars
5, Green windows will change to Red when fault occurs

♦ INSTALLATION INSTRUCTION

According to lightning protection zones concept, for installation at LPZ 0 -1 or higher. This Surge Suppressor is usually installed in distribution-box or feeder bus of UPS, protecting devices or equipment downstream. Fuse must be installed at the upstream of the Surge Suppressor or the lightning arrester to make sure that the protected system has double protection. The value of the fuse used in a Surge Suppressor system should be conformed to:

1. The value of FUSE should not be larger than the max withstand capacity of the Surge Suppressor’s backup fuse value.

2. Under the status of the max. current in the power supply & close loop circuit available current, the fuse should be able to disconnect when overloaded or short-circuited.

3. Take 1 & 2 into consideration, the fuse should be as large as possible to allow the maximum surge discharge of Surge Suppressor.

♦ INSTALLATION STEPS

1) Check the product for integrity of the package; make sure the product window indicates green.

2) Mount the Surge Suppressor on 35 mm DIN rail.

3) Connect conductors, the cross-sectional area of cable must be larger than 16mm2 . The withstand voltage value of cable is not smaller than AC500V; ensure wiring reliable.

4) If need remote alarm, it should be connected signal lines to remote signal terminal 1 and 2, or 2 and 3 (When normal,1 and 2 open, 2 and 3 close; when fault, the state is reversed).

5) After above, switch on the power supply and turn on the circuit breaker,if the Surge Suppressor’s window does not appear red, this indicates the unit is operating normally.

Regularly inspect the operating status, especially after lightning. Once the fuse upstream break, or the Surge Suppressor‘s window indicates red and 1 light display HIGH RED, electrician should check/replace the Surge Suppressor.

 
♦ Installation Diagram (4+0)
TS-385M60RM 4-Type-1-Surge-Suppressor-Cheap
♦ Installation Diagram (3+1)
TS-385M60RM 4-Type-1-Surge-Suppressor-Factory
 

♦ WARNING:  

1. The device must be installed by electrically skilled person, conforming to national standards and safety regulations.

2. It is recommended that installation should be done under power off condition.